| 1. Controller light indicator does not light up. |
|
 |
 |
- Primary power may not be on, or STANDBY switch may not be pressed.
- Circuit Protector in control panel (CP-1) may not be turned on.
|
 |
- Turn primary power and power breaker (in front of controller) on and press.

- Turn CP-1 on.

|
|
|
 |
|
|
 |
 |
 |
| 2. Controller "Dryer" does not light up. |
|
 |
 |
| To start, press each "Feeder" switch. |
 |
 |
- If indicator does not light up, press "Dryer" switch.

[Point] If drying timer is set, drying operation will start after the set time.
- If display does not appear, contact local service.
|
|
|
 |
|
|
 |
 |
| 3. Weld damage/wear on contact point of electromagnetic switch in control panel . |
|
 |
 |
| Electromagnetic switch will not function if abnormality is found. |
 |
 |
 |
Start work after stopping operation and check that breaker is off.
Those who do not have sufficient mechanical/electrical knowledge should not do any maintenance work requiring disassembly or repairing due to risk of injuries and dangers of work. |
|
- Check to find any weld damages and wear on contact points, as well as any abnormalities.

[Point] After checking, securely set white cover back on.
Reference: Tolerance - 2 million times.
|
[Abnormal Function] |
| |
Condition where magnetic points are damage and center section is caved in during machine stops or does not caved in even when pressing by hand.
|
| |
 |
Start work after stopping operation and check that breaker is off.
Those who do not have sufficient mechanical/electrical knowledge should not do any maintenance work requiring disassembly or repairing due to risk of injuries and dangers of work. |
|
- Replace switch if weld damage or wear is found, or when function is abnormal.
|

|
|
 |
|
|
 |
 |
| 4. Error code "E2" is displayed on the controller. |
|
 |
 |
Error will occur when overload current runs in blower and overload relay to switch trips.
Reference - Operation will automatically stop. |
 |
 Start work only after turning power off! |
- Check to see if electromagnetic switch does not have a thermal trip.

Click here for overload causes.
- After repairing overload in blower, press reset button on overload relay.
After eliminating cause of overload, display characters will not appear after pressing RESET.
|
|
|
 |
|
|