JL4 - User Setting Mode Parameters

No. CODE SETTING ITEMS SETTINGS SET RANGE INITIAL VALUE
1 Fd1 No. 1 Conveyance Timer
Will set conveying time of No. 1 directionTimes will vary by conveying distance, types of material and collection hopper.
Conveying will be set to conclude before
hopper becomes full
0~999sec. 5sec.
2 Fd2 No. 1 Conveyance Timer
Will set conveying time of No. 2 directionTimes will vary by conveying distance, types of material and collection hopper.
Conveying will be set to conclude before hopper becomes full
same as above same as above
3 dC1 No. 1 Discharge Timer
Will set discharge time of No. 1 collection hopper. Times will vary by type of material, size of hopper and set-up of discharge Hopper will be set to completely discharge material
0~999sec. 20sec.
4 dC2 No. 1 Discharge Timer
Will set discharge time of No. 2 collection hopper.
Times will vary by type of material,
size of hopper and set-up of discharge Hopper will be set to completely dischargematerial
same as above same as above
5 dUC Dust Cleaning Counter
Will be set to indicate notice of filter cleaning time based on number of conveyance.
Will not work when turned oFF.
When conveyance cycle reaches the set value, digital board of operation panel will indicate "E15" and notify when it is time to clean.
Setting cycle will depend on type of material and how it is used.
oFF,
1~999times
oFF
6 dUP Dust Cleaning Count

Will display actual count number of the dust cleaning counter (active).The count number is reset when set to 0.


0~999times 0