Engineering Setting Mode - Parameters

Hold the SV switch for more than 5 seconds to return to Engineering Setting Mode.
Characters on screen will change every time the SV switch is pressed during Engineering Setting Mode.
ALARM CHARACTER RANGE INITIAL
SETTING
UPPER LIMIT TEMPERATURE ALARM - DETECT DELAY TIME ULt 0~999 SEC. 0
Feed1 CONVEY ALARM DETECT COUNT LCt 0~999 50
DRYER LEVEL METER ABNORMAL COUNT FCt 0~999 20
Feed1 CONVEY ABNORMAL DETECT DELAY TIME 1Ed 0~999 MIN. 120
Feed2 CONVEY ABNORMAL DETECT DELAY TIME 2Ed 0~999 SEC. 180
Feed3 CONVEY ABNORMAL DETECT DELAY TIME 3Ed 0~999 SEC. 180
UPPER LIMIT TEMPERATURE ALARM (DRYER TEMP. DEVIATION) dUS 0~40 degrees C 10
UPPER LIMIT TEMPERATURE ALARM (REGENERATE TEMP. DEVIATION) rUS 0~40 degrees C 0
DRYER SIDE DISCONNECT DETECT TIME (DRYER) dLP 0~999 MIN. 0
REGENERATE SIDE DISCONNECT DETECT TIME (REGENERATE) rLP 0~999 MIN. 0
Feed1 LEVEL METER DEMAND DELAY L1d 0~999 SEC. 3
Feed2 LEVEL METER DEMAND DELAY L2d 0~999SEC. 3
Feed3 LEVEL METER DEMAND DELAY L3d 0~999 SEC. 3